Across the United States, fire departments are increasing enforcement of hazardous materials storage requirements. One of the most common requests facilities now receive is for a Hazardous Materials Inventory Statement (HMIS) — a detailed document required under the International Fire Code (IFC) and National Fire Protection Association (NFPA) standards.
Unfortunately, most facilities struggle to prepare an HMIS correctly. Errors in hazard classification, quantities, storage locations, or CAS numbers can lead to failed inspections, fines, or even operational shutdowns.
This guide walks you through how to prepare an HMIS accurately, avoid common mistakes, and ensure your facility is ready for fire department review.
What Is an HMIS and Why Is It Required?
An HMIS is a standardized document that lists all hazardous materials stored or used at a facility. Fire departments use HMIS documents to:
- Evaluate compliance with Maximum Allowable Quantities (MAQs)
- Assess fire and life safety risks
- Plan emergency response
- Verify proper storage and segregation
- Ensure accurate hazard classification
If your facility stores flammable liquids, corrosives, oxidizers, compressed gases, toxics, or other regulated materials, you are required to maintain an HMIS.
Why HMIS Requests Are Increasing in 2026
Several trends are driving increased enforcement:
- Fire departments are conducting more frequent inspections
- Insurance carriers are requiring updated hazardous materials documentation
- Warehouses and distribution centers are storing more chemicals than ever
- IFC/NFPA updates emphasize MAQ compliance
- Emergency responders need accurate hazard information
Many facilities are caught off guard when inspectors request an HMIS — especially if they have never prepared one before.
What Your HMIS Must Include
A compliant HMIS typically includes:
1. Chemical Name
Use the exact name from the SDS. Avoid abbreviations or trade names unless they are the only identifier.
2. CAS Number
This ensures accurate hazard classification. Missing or incorrect CAS numbers are one of the most common HMIS errors.
3. Hazard Class
Hazard classes must follow IFC/NFPA definitions, not OSHA or DOT categories. Examples include:
- Flammable Liquid
- Corrosive
- Oxidizer
- Toxic
- Pyrophoric
- Combustible Dust
4. Physical State
Solid, liquid, or gas.
5. Quantity
List the maximum quantity onsite, not average or typical amounts.
6. Storage Location
Include:
- Building
- Room
- Area
- Control area designation
7. Container Type
Examples:
- Drums
- Totes
- Cylinders
- Tanks
- Bottles
8. Storage Conditions
Such as:
- Temperature control
- Ventilation
- Separation requirements
- Fire protection features
9. SDS Reference
Fire departments often request SDS copies for all listed materials.

How to Gather Accurate HMIS Data
Preparing an HMIS requires a systematic approach. Here’s how to do it correctly.
Step 1: Conduct a Physical Inventory
Walk the facility and document:
- Every chemical
- Every container
- Every storage location
- Every quantity
Do not rely solely on purchasing records — they are almost always incomplete.
Step 2: Collect SDS Sheets
Ensure SDS sheets are:
- Current
- Complete
- From the manufacturer
- Matching the product onsite
Outdated SDS sheets lead to incorrect hazard classifications.
Step 3: Verify Hazard Classifications
Use IFC/NFPA hazard classes — not OSHA or DOT categories.
For example:
- OSHA “flammable” is not always IFC “flammable liquid”
- DOT “corrosive” may not meet IFC corrosive thresholds
- NFPA oxidizer classifications differ from DOT oxidizer classes
Misclassification is the #1 reason HMIS documents are rejected.
Step 4: Calculate Maximum Allowable Quantities (MAQs)
MAQs determine how much hazardous material you can store in each control area.
You must consider:
- Sprinkler protection
- Storage type (open vs. closed)
- Occupancy type
- Fire barriers
- Floor level
- Hazard class
If your quantities exceed MAQs, you must:
- Add fire barriers
- Reduce quantities
- Relocate materials
- Change storage methods
MAQ violations are a major enforcement focus in 2026.
Step 5: Prepare Storage Maps
Fire departments often require:
- Floor plans
- Storage area diagrams
- Control area boundaries
- Hazard class locations
- Tank and cylinder locations
Maps must be clear, accurate, and easy to read.
Step 6: Assemble the HMIS Document
A complete HMIS package includes:
- HMIS table
- SDS sheets
- Storage maps
- MAQ calculations
- Contact information
- Emergency response details
Caltha typically prepares HMIS documents as a single organized package for inspectors.
Common HMIS Mistakes (and How to Avoid Them)
1. Incorrect Hazard Classification
Using OSHA or DOT categories instead of IFC/NFPA.
2. Missing CAS Numbers
Fire departments require CAS numbers for verification.
3. Quantities Not Matching Physical Inventory
Inspectors will check actual quantities onsite.
4. Outdated SDS Sheets
SDS sheets must match the product and manufacturer.
5. Missing Storage Maps
Maps are required for emergency response planning.
6. Incorrect MAQ Calculations
MAQs are complex — many facilities miscalculate them.
7. Using Trade Names Instead of Chemical Names
Trade names often hide the true chemical identity.
8. Not Updating HMIS After Inventory Changes
HMIS must be updated whenever materials change.
How Caltha LLP Helps Facilities Prepare HMIS Documents
Caltha provides full HMIS preparation services, including:
- Facility walkthroughs
- Hazardous materials inventory development
- SDS verification
- IFC/NFPA hazard classification
- MAQ calculations
- Storage map creation
- Complete HMIS document assembly
- Fire department liaison support
Most facilities discover significant compliance gaps during HMIS preparation — and correcting them prevents costly enforcement actions.
Conclusion
Preparing an HMIS correctly is essential for fire code compliance, emergency response planning, and safe facility operations. With enforcement increasing in 2026, facilities must ensure their hazardous materials documentation is accurate, complete, and aligned with IFC/NFPA requirements.
A professionally prepared HMIS not only satisfies fire department requests but also reduces risk, improves safety, and strengthens overall compliance.